12-th diesel generator (DG-12) taken out of service

Kozloduy NPP, 15 June 2010

Nuclear Facility: Unit 1, Kozloduy NPP

Date:10.06.2010 Time:14:30

Event Title: 12-th diesel generator (DG-12) taken out of service

Event description:

Kozloduy NPP Unit 1 is in operational mode “E” without nuclear fuel in the reactor and in the spent fuel pool. A scheduled testing of the mobile diesel generator is being performed. Due to technical reasons DG-11 and DG-12 are in standby mode. According to the testing procedure, the two standby diesel generators are taken out of stand by mode. While performing the procedure DG-11 and DG 12 receive continuous start-up signals and as a result the two diesel generators’ coils for the start-up compressed air burn out. A weakness in the mobile DG testing procedure was found.

At 15:30 the burnt out coils are replaced, and the DG-11 and DG-12 standby mode is resumed. There were no violations of the operational limits and conditions.

A commission for investigation of the causes and elimination of the failure has been appointed.

 

INES rating of the event 0
*The final assessment by the NRA on the level of the event according to INES is announced following the receipt of the final report on the results from the investigation and the analysis of the event, according to art.12 of the Regulation for notification.