Taking out of service of the diesel generator from the third channel of the safety systems
Kozloduy NPP, 5 July 2010
Nuclear Facility: Unit 5, Kozloduy NPP | |
| Date: 02.07.2010 | Time:11:10 |
Event Title: Taking out of service of the diesel generator from the third channel of the safety systems | |
Event description: On 02.07.2010, Unit 5 runs on 100 % power. According to the schedule at 11:10 is initiated a consistent blowout of the diesel generators’ over-piston spaces. During the blowout of the diesel generator from the third channel of the safety systems, a water leak from the cooling of the fuel injection jet of VIII cylinder is detected. The start-up systems of channel III diesel generator are put out of stand by position and an inspection of the fuel jet is initiated. In accordance with Unit 5 Technical specifications a successful automatic staggered start-up was performed at channels I and II of the safety systems. A commission for investigation of the causes and elimination of the failure is being appointed.
| |
| INES rating of the event | 0 |