Вие сте тук: Начало en Nuclear Facilities Events in nuclear facilities Taking out of service of the diesel generator from the third channel of the safety systems

Taking out of service of the diesel generator from the third channel of the safety systems

Kozloduy NPP, 5 July 2010

Nuclear Facility: Unit 5, Kozloduy NPP

Date: 02.07.2010 Time:11:10

Event Title: Taking out of service of the diesel generator from the third channel of the safety systems

Event description:

On 02.07.2010, Unit 5 runs on 100 % power. According to the schedule at 11:10 is initiated a consistent blowout of the diesel generators’ over-piston spaces. During the blowout of the diesel generator from the third channel of the safety systems, a water leak from the cooling of the fuel injection jet of VIII cylinder is detected. The start-up systems of channel III diesel generator are put out of stand by position and an inspection of the fuel jet is initiated. In accordance with Unit 5 Technical specifications a successful automatic staggered start-up was performed at channels I and II of the safety systems. A commission for investigation of the causes and elimination of the failure is being appointed.

 

INES rating of the event 0
*The final assessment by the NRA on the level of the event according to INES is announced following the receipt of the final report on the results from the investigation and the analysis of the event, according to art.12 of the Regulation for notification.